摘要

This paper deals with a comparison of the partial discharge (PD) behavior of epoxy resin impregnated coils under high voltage and high current stress. Due to the availability of a new method, it is possible to conduct PD measurements in combination with a pulsewidth-modulation (PWM) amplifier. By this method, the PD behavior of coils under current stress can be determined. A comparison between the measurement results under voltage and current stress shows, that the PD inception voltages are higher under current stress than under voltage stress. These results suggest, that it is necessary to conduct PD measurements under current stress in order to make an accurate prediction on the PD behavior under normal operating conditions. Furthermore, a new method for locating PD sources is presented. Under special circumstances, it is possible to locate a PD source by a comparison of the PD inception voltages between voltage stress and current stress.
机译:本文对环氧树脂浸渍的线圈在高电压和高电流应力下的局部放电(PD)行为进行了比较。由于新方法的可用性,可以结合脉宽调制(PWM)放大器进行PD测量。通过这种方法,可以确定线圈在电流应力下的局部放电性能。在电压应力和电流应力下的测量结果之间的比较表明,电流应力下的PD起始电压高于电压应力下的PD起始电压。这些结果表明,有必要在当前压力下进行局部放电测量,以便对正常工作条件下的局部放电行为做出准确的预测。此外,提出了一种定位局部放电源的新方法。在特殊情况下,可以通过比较电压应力和电流应力之间的PD起始电压来定位PD源。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号