The results of aging experiments under combined electrical, mechanical (vibration), and thermal stresses on epoxy-bonded mica insulation are presented. Actual 11-kV machine coils designed for use in 1 MW rotating machines are used as the specimens. Both diagnostic and destructive tests were carried out to assess the amount of aging. It was observed that the incremental loss tangent and partial discharge energy per cycle increased monotonically with time of aging and that the dielectric strength fell monolithically, thus indicating a high degree of correlation between these properties.
机译:给出了在结合有电,机械(振动)和热应力的环氧粘结云母绝缘材料上进行的老化实验的结果。设计用于1 MW旋转电机的实际11 kV电机线圈用作样本。诊断和破坏性测试均进行以评估老化程度。观察到,随着时间的推移,每个周期的增量损耗角正切和部分放电能量随时间单调增加,并且介电强度整体下降,因此表明这些特性之间的高度相关性。