【24h】

A study of fast transients in gas insulated substations

机译:气体绝缘变电站的快速瞬变研究

获取原文

摘要

Experimental and theoretical techniques are being used to investigate the response of gas-insulated substations (GISs) to fast transients. Sensors were developed to record fast transient waveforms accurately over a wide frequency range. Their performance under fast transient conditions was verified using a D-dot probe with a known response. Good agreement was recorded by instrumentation with a 200-MHz bandwidth. A computer code was developed to enable electrical stresses in a GIS under fast transient conditions to be studied. The program solves Maxwell's equations in two dimensions using a finite-difference method. The electric field structure around insulating barriers was studied, and initial results are presented.
机译:实验和理论技术正用于研究气体绝缘变电站(GIS)对快速瞬变的响应。传感器的开发是为了在很宽的频率范围内准确记录快速瞬态波形。使用具有已知响应的D点探针验证了它们在快速瞬态条件下的性能。使用200 MHz带宽的仪器记录了良好的一致性。开发了一种计算机代码,可以研究快速瞬态条件下GIS中的电应力。该程序使用有限差分法二维求解麦克斯韦方程。研究了绝缘势垒周围的电场结构,并给出了初步结果。

著录项