首页> 外文会议>Asia Conference on Power and Electrical Engineering >Comparative analysis of the effects of different resistance reduction measures based on CDEGS calculations
【24h】

Comparative analysis of the effects of different resistance reduction measures based on CDEGS calculations

机译:基于CDEGS计算的不同阻力降低措施影响的比较分析

获取原文

摘要

Based on the actual measured soil resistivity in a substation, this paper uses CDEGS to calculate and analyze the effects of deep well grounding, oblique well grounding, and small well grounding on improving the grounding performance of the grounding grid. Through the comparison of main parameters such as grounding resistance, ground potential rise, touch voltage and step voltage, it can be known: The oblique well grounding can play the role of a deep well grounding, and it can also effectively expand the area of the grounding grid without the need for land acquisition, and the mutual shielding effect of the oblique grounding electrode is much smaller than that of the deep grounding electrode; The small well grounding is more effective in terms of the effect of the touch voltage at the edge of the substation.
机译:基于实际测量的土壤电阻率在变电站中,本文使用CDEG计算和分析深井接地,倾斜良好接地和小良好接地对提高接地网格的接地性能的影响。 通过比较接地电阻,地电位上升,触摸电压和阶梯电压的主要参数,可以知道:倾斜良好的接地可以发挥深井接地的作用,也可以有效地扩展面积 接地网格无需陆地采集,倾斜接地电极的互屏蔽效果远小于深接地电极的屏蔽效果; 在变电站边缘处的触摸电压的影响方面,小良好的接地更有效。