Average Current Sharing Control Strategy for Parallel Operation of UPS with Low Bandwidth Communication

机译:低带宽通信UPS并联运行的平均均流控制策略

获取原文

摘要

This paper analyzes the stability of average current sharing (ACS) control for parallel uninterruptible power supply (UPS) with low bandwidth communication (LBC). In the ACS method, the LBC causes the instability problem due to its phase lags. Also, it is related to the system output impedance because it appears on the poles which may cause instability issues. To analyze the output impedance effect in the ACS, dual-loop voltage controller which has different output impedance as different inner feedback currents, is adopted. Simulations and experimental results on the two parallel 15 kVA three phase inverters show the validation of stability analysis and effectiveness of the proposed method.
机译:本文分析了具有低带宽通信(LBC)的并行不间断电源(UPS)的平均电流共享(ACS)控制的稳定性。在ACS方法中,LBC由于其相位滞后而导致不稳定问题。而且,它与系统输出阻抗有关,因为它出现在极点上,这可能会导致不稳定问题。为了分析ACS中的输出阻抗效应,采用了双环路电压控制器,该控制器具有不同的输出阻抗和不同的内部反馈电流。在两个并联的15 kVA三相逆变器上进行的仿真和实验结果表明,所提方法具有稳定性分析的有效性和有效性。