THE IMPACT OF MAGNETICALLY NONLINEAR IRON CORE CHARACTERISTICS ON RESPONSES OF A THREE-PHASE POWER TRANSFORMER DYNAMIC MODEL

机译:磁性非线性铁芯特性对三相电力变压器动力学模型响应的影响

获取原文

摘要

This work analyses the impact of magnetically nonlinear iron core characteristics on responses calculated by a three-phase power transformer dynamic model. The iron core characteristics are determined in different way. Their impact on calculated responses is evaluated by the comparison of calculated responses with the measured ones. Results presented in the paper show that a very good agreement between the measured results and the calculated ones can be achieved only if the complete harmonic content of measured currents is used for determining magnetically nonlinear iron core characteristics of the transformer.
机译:该工作分析了磁性非线性铁芯特性对三相电力变压器动力学模型计算的响应的影响。铁芯特性以不同的方式确定。它们对计算响应的影响是通过对测量的计算的计算的比较来评估。本文介绍的结果表明,只有在测量电流的完全谐波含量用于确定变压器的磁性非线性铁芯特性时,才能实现测量结果与计算的结果非常好。