In this paper, simulation of large motor drives with three-level neutral point clamped converters and testing results of converter transformer differential protection are presented. The protected converter transformer is used for supply of active front end converters. The converter transformer itself must be protected by a relay being able to operate with highly distorted signals by higher harmonics. One should be aware that high content of harmonics (2nd, 5th) may cause problem with sensitivity and stabilization of protection. An appropriate simulation model of the converter transformer and three-level neutral point clamped converters with adequate control was developed in MATLAB/Simulink environment. Testing results of transformer differential protection operation for various disturbances are presented.
机译:本文介绍了具有三电平中性点钳位转换器的大型电动机驱动器的仿真以及转换器变压器差动保护的测试结果。受保护的转换器变压器用于为有源前端转换器供电。转换器变压器本身必须受到继电器的保护,该继电器必须能够以较高的谐波对高度失真的信号进行操作。请注意,谐波含量高(2 nd ,5 )可能会导致灵敏度和保护稳定性问题。在MATLAB / Simulink环境中,开发了具有适当控制能力的变流变压器和三级中性点钳位变流器的合适仿真模型。给出了针对各种干扰的变压器差动保护运行的测试结果。