Dielectric Response Analysis of Mineral Oil Immersed Transformer, Natural Ester(FR3) Immersed Transformer, and Palm Oil Immersed Transformer

机译:矿物油浸式变压器,天然酯(FR3)浸入式变压器和棕榈油浸入式变压器的介电响应分析

获取原文

摘要

Currently alternative liquid insulation such as natural ester (FR3) is widely used as distribution transformer insulation because it provides outstandingly dielectric characteristics and natural friendly including highly affordable fire safety. Besides, palm oil is interesting liquid insulation for such transformers because of its distinguish dielectric properties. To analyze the dielectric properties of insulating material, polarization and depolarization current (PDC) measurement is one of the widely accepted non-destructive test technique. This paper presents the dielectric response analysis for the insulation system of a mineral oil immersed transformer, a natural ester (FR3) immersed transformer, and a palm oil immersed transformer by analyzing PDC test results. Three identical single phase transformers with 22kV/460V 30 kVA rated were designed and constructed. The first transformer was fully filled with mineral oil. The second and the third transformer was fully filled with natural ester (FR3) and palm oil respectively. After finishing the construction process, PDC measurement technique was applied for these transformers. The PDC measurement were performed for three case studies as follows: 1) dielectric response for the insulation between high voltage winding and low voltage winding, 2) dielectric response of high voltage winding insulation and low voltage connected to ground 3) dielectric response of high voltage and low voltage winding insulation by which the high voltage lead was connected to the low voltage lead. From the test results, it can be concluded that the dielectric response of the insulation system of the mineral oil immersed transformer was obviously different compared with that of the natural oil (FR3) immersed transformer and the palm oil immersed transformer. Moreover, the PDCs obtained from the tests were also analyzed and reported in this paper.
机译:当前,替代液体绝缘材料(例如天然酯(FR3))被广泛用作配电变压器绝缘材料,因为它具有出色的介电特性和自然友好性,其中包括价格合理的防火安全性。此外,棕榈油因其独特的介电性能而成为此类变压器有趣的液体绝缘材料。为了分析绝缘材料的介电特性,极化和去极化电流(PDC)测量是一种广泛接受的无损测试技术。本文通过分析PDC测试结果,介绍了矿物油浸式变压器,天然酯(FR3)浸入式变压器和棕榈油浸入式变压器的绝缘系统的介电响应分析。设计并制造了三台相同的额定电压分别为22kV / 460V 30 kVA的单相变压器。第一台变压器充满了矿物油。第二个和第三个变压器分别充满了天然酯(FR3)和棕榈油。在完成施工过程后,将PDC测量技术应用于这些变压器。针对以下三个案例研究进行了PDC测量:1)高压绕组和低压绕组之间绝缘的介电响应,2)高压绕组绝缘和接地低压的介电响应3)高压的介电响应低压绕组绝缘层,通过该绝缘层将高压引线连接到低压引线。从测试结果可以得出结论,矿物油浸式变压器的绝缘系统的介电响应与天然油(FR3)浸入式变压器和棕榈油浸入式变压器的绝缘系统明显不同。此外,本文还分析并报告了从测试中获得的PDC。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号