首页> 外文会议>IEEE International Conference on Dielectric Liquids >Partial Discharge Characteristics caused by Metallic Particles under DC voltage on Oil Immersed Insulation
【24h】

Partial Discharge Characteristics caused by Metallic Particles under DC voltage on Oil Immersed Insulation

机译:油浸绝缘上直流电压下金属颗粒引起的局部放电特性

获取原文

摘要

Development of direct current (DC) power equipment is necessary for spreading DC power transmission systems in order to increase the amount of renewable energy. The insulation performance of power equipment deteriorates by various defects. In particular, when a metallic particle is present inside the power equipment, such as oil immersed transformer, the partial discharge inception voltage (PDIV) decreases greatly. For AC transformers, many investigations have been made on partial discharge (PD) caused by metallic particles. On the other hand, there are few reports on PD under DC voltage. In this paper, we have investigated PD characteristics caused by metallic particles under DC voltage in the oil / pressboard (PB) composite insulation system. Three results were obtained from our experiments. First, PDIV under positive DC voltage was lower than under negative DC voltage due to the difference of the discharge formations, etc. On the other hand, PDIV under positive DC voltage was the same as PDIV under AC voltage in the oil insulation setup. Secondly, PDIV was almost constant if the curvature radius was 10 $mu$m or less due to the electric field relaxation effect caused by space charges in the vicinity of the needle tip. Finally, the electric field in the vicinity of the needle tip at the PDIV in oil was in the range of 200~400 kV/mm, regardless of the gap distance, the type of the applied voltage: AC or positive DC voltage, and the insulation system: only oil system or oil / PB composite system. That is, the condition for starting PD in the presence of metallic particle is determined by the electric field in the vicinity of the tip of the metallic particle regardless of the gap distance, the type of the applied voltage, and the insulation system.
机译:为了扩展直流输电系统,必须开发直流(DC)电力设备,以增加可再生能源的数量。电力设备的绝缘性能由于各种缺陷而恶化。尤其是当电力设备内部(例如油浸式变压器)中存在金属颗粒时,局部放电起始电压(PDIV)会大大降低。对于交流变压器,已经对由金属颗粒引起的局部放电(PD)进行了许多研究。另一方面,关于直流电压下的局部放电的报道很少。在本文中,我们研究了油/压纸板(PB)复合绝缘系统中直流电压下金属颗粒引起的局部放电特性。从我们的实验中获得了三个结果。首先,由于放电形式的差异等,正直流电压下的PDIV低于负直流电压下。另一方面,在油绝缘装置中,正直流电压下的PDIV与交流电压下的PDIV相同。其次,由于由针尖附近的空间电荷引起的电场松弛效应,如果曲率半径为10μm或更小,PDIV几乎恒定。最后,不管间隙距离,所施加电压的类型为交流还是正直流电压以及所施加的电压为多少,油中PDIV的针尖附近的电场都在200〜400 kV / mm的范围内。绝缘系统:仅油系统或油/ PB复合系统。即,在金属粒子的存在下开始PD的条件由金属粒子的尖端附近的电场决定,而与间隙距离,施加电压的类型和绝缘系统无关。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号