Fault Detection Technology and Analysis of 10 kV XLPE Power Cable

机译:10 kV交联聚乙烯电力电缆故障检测技术与分析

获取原文

摘要

With the rapid development of power infrastructure, cross-linked polyethylene (XLPE) power cable plays an increasingly important role in urban distribution networks. Therefore, it is of great significance to test and diagnose the performance of XLPE cable insulation to ensure the reliability of cable operation. The field test of a cable line which has been running for 8 years using the technology of oscillating partial discharge combined with 0.1 Hz ultra-low frequency dielectric loss is introduced in this paper. The results show the abnormal partial discharge of the middle joint at 95m away from the outlet of the substation. Moreover, standard deviation and dielectric loss change rate under U0 voltage are all over the normal range, and the cable has water tree aging. The research results can provide direction for the physical and chemical analysis of cable and further analysis of aging degree.
机译:随着电力基础设施的快速发展,交联聚乙烯(XLPE)电力电缆在城市配电网络中扮演着越来越重要的角色。因此,对XLPE电缆绝缘性能进行测试和诊断对保证电缆运行的可靠性具有重要意义。本文介绍了使用振荡局部放电技术结合0.1 Hz超低频介电损耗对已运行8年的电缆线进行的现场测试。结果表明,离变电站出口95m处的中间接头局部放电异常。而且,U0电压下的标准偏差和介电损耗变化率均在正常范围内,并且电缆有水树老化现象。研究结果可为电缆的理化分析和老化程度的进一步分析提供指导。