首页> 外文会议>International Conference on Systems and Informatics >The Location of Partial Discharge Source in the Power Transformer with UHF Sensors
【24h】

The Location of Partial Discharge Source in the Power Transformer with UHF Sensors

机译:带UHF传感器的电力变压器中局部放电源的位置

获取原文

摘要

This paper discusses the theory of the location of the partial discharge and carries out a PD experiment with a real power transformer. Five Ultra high frequency (UHF) sensors are used to detect the PD source. The location of the PD source can be analyzed and calculated by establishing a power transformer model and collecting the electromagnetic signals generated from the PD source. A comparison between the actual PD source and the estimated location is also made. Time difference of arrival (TDOA) of distinct signals collected by different sensors can be used to search for the PD location. Distance equations are formulated based on the geometrical relationship and the 2-norm theory. To determine the time difference, first peak method is used in the power transformer model.
机译:本文讨论了局部放电位置的理论,并使用真实的电力变压器进行了局部放电实验。五个超高频(UHF)传感器用于检测PD源。通过建立电力变压器模型并收集从PD源产生的电磁信号,可以分析和计算PD源的位置。还对实际PD源和估计位置进行了比较。由不同传感器收集的不同信号的到达时间差(TDOA)可用于搜索PD位置。距离方程是基于几何关系和2-范数理论制定的。为了确定时间差,在电源变压器模型中使用了第一峰值方法。