首页> 外文会议>International Conference on Smart City and Systems Engineering >Mechanism Analysis and Prevention of Transmission Line Tripping Caused by the Falling of Box for Bird Guard
【24h】

Mechanism Analysis and Prevention of Transmission Line Tripping Caused by the Falling of Box for Bird Guard

机译:护鸟箱掉落引起输电线路跳闸的机理分析及预防

获取原文

摘要

In recent years, there have been a number of tripping events caused by the falling of boxes for bird guard in Jiangxi Power Grid. Scene investigation and laboratory test have been carried out to analyze the characteristics of fault tripping and perform thickness measurement, performance testing and TGA test analysis to a sample box for bird guard in this paper. It is found that the main reasons for the falling of boxes for bird guard are premature aging of them and unscientific fixing of them and the main reasons for premature aging is the too low initial decomposition temperature of material and too thin unsaturated resin. In addition, a simulation study is performed to transmission line tripping caused by the falling of boxes for bird guard in this paper. It is concluded that the direct cause of the tripping is the occurrence of concentrated water columns.
机译:近年来,由于江西电网鸟类保护盒掉落而引起的多次跳闸事件。本文进行了现场调查和实验室测试,以分析故障跳闸的特征,并对鸟类保护装置的样品盒进行厚度测量,性能测试和TGA测试分析。发现用于鸟类保护装置的盒子掉落的主要原因是它们的过早老化和它们的不科学固定,并且过早老化的主要原因是材料的初始分解温度太低以及不饱和树脂太薄。此外,本文针对鸟类保护盒掉落引起的传输线跳闸进行了仿真研究。结论是,跳闸的直接原因是浓缩水柱的出现。