In order to test whether the new GIS (gas insulated enclosed metal switch) equipment have operation conditions or not, at present, the effective way is to carry out field AC withstand voltage test. AC voltage withstand test is mainly the frequency conversion series resonance method. It is very important to accurately calculate the load carrying capacity of the pressure test device when it is necessary to spend a lot of time on the preparation of the field test. When the circuit is in the non-resonant state, it is difficult to determine the relationship between capacitance and voltage. In this paper, a method is proposed to calculate the relationship between the maximum capacitance and voltage under the condition of limiting frequency. The method has been applied to field experiments, and the method is proved to be correct and effective.
机译:为了测试新的GIS(气体绝缘封闭金属开关)设备是否具有运行条件,目前,有效的方法是进行现场交流耐压测试。交流耐压测试主要是变频串联谐振法。当需要花费大量时间准备现场测试时,准确计算压力测试设备的承载能力非常重要。当电路处于非谐振状态时,很难确定电容和电压之间的关系。本文提出了一种在极限频率条件下计算最大电容与电压之间关系的方法。该方法已应用于野外实验,证明了该方法的正确性和有效性。