首页> 外文会议>IEEE Holm Conference on Electrical Contacts >Temperature rise of canted spring contacts during fault current
【24h】

Temperature rise of canted spring contacts during fault current

机译:故障电流期间弹簧倾斜触点的温升

获取原文

摘要

During the breaking test of a high voltage circuit breaker, a canted spring contact connecting the busbars of the switchgear melted. This event provided a good opportunity to test the reliability of finite element (FE) temperature rise calculations based on a transient coupled thermal-electromagnetic (EM) model. To properly include the Joule-losses at the tiny contact points in a time-varying ANSYS FE analysis, we had to devise a unique method of contact resistance modelling. The paper shortly describes this method and shares our experience we obtained from the case study of canted spring contact temperature rise.
机译:在高压断路器的断开测试期间,倾斜弹簧触点连接开关设备的汇流磁石熔化。该事件提供了基于瞬态耦合的热电磁(EM)模型来测试有限元(FE)温度升高计算的可靠性的良好机会。为了在时变的ANSYS FE分析中正确地包括微小接触点处的焦耳损失,我们必须设计一种独特的接触电阻建模方法。本文不久介绍了这种方法,并分享了我们从倾斜弹簧接触温度升高的案例研究中获得的经验。