首页> 外文会议>IEEE Holm Conference on Electrical Contacts >The effect of the axial magnetic field structure on the threshold welding current for closed axial magnetic field vacuum interrupter contacts
【24h】

The effect of the axial magnetic field structure on the threshold welding current for closed axial magnetic field vacuum interrupter contacts

机译:轴向磁场结构对闭合轴向磁场真空灭弧室触头阈值焊接电流的影响

获取原文

摘要

There are two designs of large area, vacuum interrupter contacts: the transverse magnetic field (TMF) contact and the axial magnetic field (AMF) contact. These contacts are required to perform a wide variety of roles within vacuum circuit breakers. One duty is to pass short-circuit currents with the vacuum interrupters' contacts closed for a period of time (1 to 4 seconds), after which the circuit breaker's mechanism must be able to open the contacts. Thus, the possibility of contact welding must be minimized. The flow of current through practical contacts generates a repulsive blow-off force, which has to be balanced by a closing force from the circuit breaker mechanism plus the force from atmospheric pressure acting on the vacuum interrupter's bellows. The axial magnetic field (AMF) vacuum interrupters have an additional attractive force because of the parallel currents flowing in the two AMF coils behind the contacts' faces. This force is calculated using three- dimensional finite element analysis (FEA) for three practical AMF designs using a contact diameter of 62 mm and a current of 31.5 kA (45.5 kA peak). The extra attractive forces are then combined with the other forces acting on the closed vacuum interrupter contacts to calculate the threshold welding current: the current above which the contacts will form a weld. Calculations of the total closing force compares the difference in the threshold welding current between the three AMF contact designs.
机译:大面积的真空断路器触头有两种设计:横向磁场(TMF)触头和轴向磁场(AMF)触头。这些触点在真空断路器中起着各种各样的作用。一种职责是在真空断路器的触头闭合状态下持续一段时间(1到4秒),以通过短路电流,然后断路器的机构必须能够断开触头。因此,必须最小化接触焊接的可能性。流过实际触点的电流会产生排斥的吹脱力,该吹脱力必须通过断路器机构的闭合力和作用在真空灭弧室波纹管上的大气压力来平衡。轴向磁场(AMF)真空灭弧室具有额外的吸引力,这是因为在触点面后面的两个AMF线圈中流过并联电流。对于三种实际的AMF设计,使用三维有限元分析(FEA)来计算此力,使用的接触直径为62 mm,电流为31.5 kA(峰值为45.5 kA)。然后,将额外的吸引力与作用在闭合的真空灭弧室触点上的其他力相结合,以计算阈值焊接电流:在该电流之上,触点将形成焊接。总闭合力的计算比较了三种AMF触点设计之间的阈值焊接电流的差异。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号