首页> 外文会议>International Universities Power Engineering Conference >MVAC submarine cable, magnetic fields measurements and analysis
【24h】

MVAC submarine cable, magnetic fields measurements and analysis

机译:MVAC海底电缆,磁场测量和分析

获取原文

摘要

The recent concerns for the environment have caused an increase in the number of offshore wind farms. These farms use submarine cables to transmit the power onshore. Recent studies show that the cables are being over-dimensioned when using the standard formulas for their design, given by the IEC Standard 60287. Researchers believe that the wire armour of three phased submarine cables is the reason for the inaccurate calculations by the standard. Studies show that the magnetic behaviour of these cables are changed due to the wire armour. In order to investigate this hypothesis, this paper intends to supply the theoretical research with data from magnetic field measurements on a wire armoured 3-phase submarine cable, together with an investigation of the induced currents in the different cable components. The influence of the physical arrangement of the armour wires on the electric behaviour is also investigated, since several researchers believe that the twisting of the armour wires result in zero net induced voltage over one helix length. This is shown to be valid for the tested cable. Finally a replica of the armour has been built with just a single conductor in the centre. This setup was used to measure how the magnetic field varies between wires, above a wire, inside the wire arrangement and at sections without armour. The magnetic field tests are compared to a COMSOL model of the specified cable showing good compliance between experimental and simulated results. It is concluded that at low core currents, the magnetic field is not a dominant factor to the results and the behaviour of a wire armour and pipe armour is similar.
机译:最近对环境的关注导致海上风电场的数量增加。这些农场使用海底电缆在岸上传输电力。最近的研究表明,使用IEC标准60287给出的标准公式进行设计时,电缆尺寸过大。研究人员认为,三相海底电缆的铠装是该标准计算不准确的原因。研究表明,由于电缆铠装,这些电缆的磁性能发生了变化。为了研究这个假设,本文旨在为理论研究提供来自铠装三相海底电缆的磁场测量数据,以及对不同电缆组件中的感应电流的研究。还研究了铠装线的物理布置对电性能的影响,因为一些研究人员认为铠装线的扭曲会导致在一个螺旋长度上产生零净感应电压。这显示对测试的电缆有效。最终,仅在中心放置了一根导体,就制作出了装甲的复制品。该设置用于测量导线之间,导线上方,导线布置内部以及无铠装部分的磁场如何变化。将磁场测试与指定电缆的COMSOL模型进行比较,显示出实验结果与模拟结果之间的良好一致性。结论是,在低铁心电流下,磁场不是决定结果的主要因素,导线铠装和管道铠装的行为相似。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号