During the design and construction phases of nuclear power plants (NPPs), fire protection design principle requires that the safety classified equipment within the nuclear island, the service water pump building and galleries should meet the safety goal whenever a design basis fire occurs. The design of passive facilities, such as structure of buildings and physical separation of equipment, should prevent one single fire from failing all redundant equipment of the same safety function. When one single fire fails all redundant equipment of the same function, it is called a fire common mode. By performing fire vulnerability analysis of fire areas or fire zones, analysts can identify the possible fire common modes, and confirm if they are acceptable or not through further analysis. For NPPs in operation, the vulnerability analysis can be performed by examining the details of plant specific cables and equipment. The confirmed unacceptable common modes should be modified or protected through changing cable routing or adding fire coating, etc. Moreover, by employing internal fire probabilistic risk analysis (PRA), analysts can categorize the identified fire common modes according to severity, assess the changes in the risk of internal fire after elimination, and evaluate the benefit of performing elimination, which provides reference for engineering modification by showing the order of priority of each modification. This article introduces the process of identifying fire common modes, performing internal fire PRA and providing suggestions of modification, and illustrates the application of internal fire PRA in eliminating fire common modes and enhancing the safety level of NPPs.
机译:在核电厂(NPP)的设计和建造阶段,防火设计原则要求,一旦发生设计基准火灾,核岛,服务水泵建筑物和走廊中的安全分类设备应达到安全目标。被动设施的设计,例如建筑物的结构和设备的物理隔离,应防止一次火灾使具有相同安全功能的所有冗余设备失效。当一次火灾使具有相同功能的所有冗余设备发生故障时,称为火灾共模。通过对火灾区域或火灾区域进行火灾易损性分析,分析人员可以识别可能的火灾共模,并通过进一步分析来确认是否可接受。对于正在运行的NPP,可以通过检查工厂特定电缆和设备的详细信息来执行漏洞分析。确认的不可接受的共模应通过更改电缆布线或增加防火涂层等方式进行修改或保护。此外,通过采用内部火灾概率风险分析(PRA),分析人员可以根据严重程度对识别出的火灾共模进行分类,评估其变化。消除后的内部火灾风险,并评估消除的好处,通过显示每个修改的优先级顺序,为工程修改提供参考。本文介绍了确定火灾常见模式,执行内部火灾PRA的过程并提供了修改建议,并说明了内部火灾PRA在消除火灾常见模式和提高核电厂安全水平方面的应用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号