首页> 外文会议>International Conference on Measuring Technology and Mechatronics Automation >GIS Insulation Fault Diagnosis Based on Detection of SF6 Decomposition Products
【24h】

GIS Insulation Fault Diagnosis Based on Detection of SF6 Decomposition Products

机译:基于SF6分解产物检测的GIS绝缘故障诊断

获取原文

摘要

Partial discharge (PD) and partial over-thermal (POT) are the major failure modes of gas insulated switchgear (GIS), the measurement of which are among the most important methods of diagnosing insulation failure in GIS. The decomposition products of SF6 under PD and POT can be used to detect and recognize PD and POT, but feature parameters must be selected first. In this paper, three kinds of PD defect models and a gas chamber were designed to simulate PD. A heating rod and a real disconnector chamber were used to simulate POT. By reviewing the decomposition mechanism of SF6 and analyzing the experiment results, three concentration ratios were chosen as feature parameters, that is, c(SO2F2+SOF2+SO2)/c(CO2), c(SOF2)/c(SO2) and c(SOF2+SO2)/c(SO2F2). The physical significance of the proposed three concentration ratios was also analyzed. Finally, fuzzy c-means clustering was employed to test the effectiveness of using these three concentration ratios as feature parameters to expose the difference between PDs and POT. Results showed that the proposed feature parameters performed well and could successfully recognize different kinds of PD and POT.
机译:局部放电(PD)和局部过热(POT)是气体绝缘开关设备(GIS)的主要故障模式,对其进行测量是诊断GIS绝缘故障的最重要方法之一。可以将PD6和POT下的SF6分解产物用于检测和识别PD和POT,但是必须首先选择特征参数。本文设计了三种局部放电缺陷模型和一个气室来模拟局部放电。加热棒和实际的隔离室用于模拟POT。通过回顾SF6的分解机理并分析实验结果,选择了三个浓度比作为特征参数,分别为c(SO2F2 + SOF2 + SO2)/ c(CO2),c(SOF2)/ c(SO2)和c (SOF2 + SO2)/ c(SO2F2)。还分析了所提出的三个浓度比的物理意义。最后,采用模糊c均值聚类法测试这三种浓度比作为特征参数的有效性,以揭示PD和POT之间的差异。结果表明,所提出的特征参数表现良好,可以成功识别出不同种类的PD和POT。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号