Current and voltage behaves like a fault during power swing condition. Distance relay which sense to operate due to change in impedance may be falsely operated in power swing. Therefore a power swing block is necessarily used in distance relay for security purpose to avoid mal-operation during power swing. During power swing all types of fault such as symmetrical, unsymmetrical and high resistance fault are simulated through PSCAD software to test this technique. This method is tested accurate and fast.
机译:在电源摆幅条件下,电流和电压的行为就像故障一样。在功率摆幅中,由于阻抗变化而感觉到要动作的距离继电器可能会误操作。因此,出于安全目的,必须在距离继电器中使用功率摆幅块,以避免功率摆幅期间的误操作。在功率摆幅期间,通过PSCAD软件对所有类型的故障(例如对称故障,非对称故障和高阻故障)进行仿真,以测试该技术。该方法经过准确,快速的测试。