【24h】

Voltage transients measurements and power line communication

机译:电压瞬变测量和电力线通信

获取原文

摘要

Power line communication (PLC) connects energy producers with energy consumers. In the European Union stricter guidelines are under development to limit disturbances in the 2-150 kHz frequency range, because devices utilising PLC do not work. This study measured voltage transients in 22 locations and identified sources for noise. Home environments and public buildings were measured. Measurements were conducted in the frequency range of 150 kHz-500 kHz (according to EN 55011 to EN 55022) and in the lower frequency range of 3 kHz to 95 kHz. Results indicate that voltage transients are generated mostly by switching mode power supplies, pumps, rectifiers, inverters and even low quality smart meters. Several of these devices exceeded PLC standard level, 122 dBμV. Additionally we demonstrate that basic power quality recordings do not provide enough information to mitigate PLC problems occurring within microseconds and frequency specific voltage transient measurements are needed.
机译:电力线通信(PLC)将能源生产者与能源消耗者联系起来。在欧盟,由于使用PLC的设备无法正常工作,正在制定更严格的准则以限制2-150 kHz频率范围内的干扰。这项研究测量了22个位置的电压瞬变,并确定了噪声源。测量了家庭环境和公共建筑。在150 kHz-500 kHz的频率范围(根据EN 55011至EN 55022)和3 kHz至95 kHz的较低频率范围内进行测量。结果表明,电压瞬变主要由开关电源,泵,整流器,逆变器甚至低质量的智能电表产生。这些设备中有几个超出了PLC标准水平,即122dBμV。此外,我们证明基本电能质量记录不能提供足够的信息来缓解微秒内发生的PLC问题,并且需要特定频率的电压瞬态测量。