Investigation of bipolar block emergency in UHVDC convertor station caused by lightning stroke

机译:雷击雷控电台双极块应急调查

获取原文

摘要

It is noteworthy that bipolar block emergencies of the ±800kV UHVDC system in China happened twice within two years caused by lightning strokes. To recur and investigate the mechanism of such emergencies, lightning transient performance and relative electromagnetic interference (EMI) in the UHVDC system are investigated. Wide-band circuit models of major UHVDC equipments are set for calculation, while the lightning stroke shielding failure process and transmission corona loss are also considered during the simulation. By combining the fault records in the converter station and simulation results , possible ways of EMI into the secondary system produced by primary circuit lightning transient are analyzed. The results would help explain the cause of such bipolar block emergency and provide reference for protection methods of lightning caused EMI in UHVDC system.
机译:值得注意的是,中国±800kV UHVDC系统的双极块紧急情况发生了两次雷电行李造成的两倍。为了重现并调查这种紧急情况的机制,研究了UHVDC系统中的雷电瞬态性能和相对电磁干扰(EMI)。主要UHVDC设备的宽带电路模型被设定为计算,而在模拟期间也考虑雷击屏蔽故障过程和传输电晕损失。通过将转换器站和仿真结果中的故障记录相结合,分析了通过主电路避雷瞬变产生的二级系统的EMI的可能方式。结果将有助于解释这种双极块应急的原因,并为UHVDC系统中闪电引起的保护方法提供参考。