Theoretical calculations have been done for determining the low frequency earth resistance of a set of individual electrodes, once the electrode dimensions, installation geometry and soil resistivity profile are given. Accuracy of theoretical estimations was tested by taking measurements of 25 electrodes installed at various soil conditions and environments. It has been found that in most of the site locations, especially vegetation and built-up environments, model predictions deviate considerably from measured values. Three dimensional soil resistivity map of a given land mass is essentially needed in predicting the final earth resistance of a given electrode system. Existing models are not able to produce the large variation in earth resistance, specifically due to the non-uniformity of soil resistivity and probably due to the contact resistance between electrode and surrounding soil. The outcome of this study will immensely be helpful in designing earthing systems for a given installation even at pre-construction stage.
机译:一旦给出了电极尺寸,安装几何形状和土壤电阻率曲线,就完成了用于确定一组单独电极的低频接地电阻的理论计算。通过在各种土壤条件和环境下安装25个电极来测试理论估计的准确性。已经发现,在大多数场地位置,尤其是植被和内置环境,模型预测偏离测量值很大。在预测给定电极系统的最终接地电阻之前,基本上需要给定陆地的三维土壤电阻率图。现有型号不能产生抗地电阻的大变化,特别是由于土壤电阻率的不均匀性,并且可能是由于电极和周围土壤之间的接触电阻。即使在预施工阶段,本研究的结果也将对设计用于特定安装的接地系统非常有用。