首页> 外文会议>International Conference on Lightning Protection >FDTD simulation of back-flashover at the transmission-line tower struck by lightning considering ground-wire corona
【24h】

FDTD simulation of back-flashover at the transmission-line tower struck by lightning considering ground-wire corona

机译:考虑地线电晕的雷电击中输电塔回闪的FDTD模拟

获取原文
获取外文期刊封面目录资料

摘要

In this paper, we have simulated back-flashover at transmission line tower struck by lightning in the presence of corona emanated at the ground wire. In the simulations, three two-circuit 60-m high towers, separated by 400 m, with two overhead ground wires, and six phase conductors (two three-phase circuits) are employed. A simplified (engineering) model of corona discharge is applied to the analysis of transient voltages across insulators of transmission line. Back-flashover is assumed to occur at upper-, middle-, or lower phase. On the basis of computed results, the effect of corona space charge emanated from ground wires on transient voltages across insulators in the presence of back-flashover is discussed.
机译:在本文中,我们模拟了在接地线发出电晕的情况下,雷电击中的输电线路塔的反向闪络。在仿真中,使用了三个两回路60米高的铁塔,相隔400 m,带有两根架空地线和六个相导体(两个三相电路)。电晕放电的简化(工程)模型用于分析传输线绝缘子两端的瞬态电压。假定反向闪络发生在上,中或下相位。根据计算结果,讨论了在存在反向闪络的情况下,从地线发出的电晕空间电荷对绝缘子两端的瞬态电压的影响。