This paper proposes an integrated reclosing technique that combines the merits of adaptive reclosing technique (ART) and the optimal reclosing technique (ORT) to improve the transient stability problem. The ART discriminate the fault nature, and detects the instant of arc extinguished by using the harmonics components in the faulted phase voltage using wavelet packet transform (WPT). The ORT is resulting from the load angle of the synchronous generator. The proposed integrated technique is dependent on adaptive threshold level and on the information that captured from one end only. The performance of the integrated reclosing method is assessed compared to conventional reclosing schemes in terms of voltage and speed indices. The Integrated method is confirmed by using MATLAB/SIMULINK to simulate a single machine infinite bus system model (SIME). The output results indicate that the proposed reclosing method can enhance the transient stability.
机译:本文提出了一种综合重合闸技术,该技术结合了自适应重合闸技术(ART)和最佳重合闸技术(ORT)的优点,以改善瞬态稳定性问题。 ART识别故障性质,并通过小波包变换(WPT)使用故障相电压中的谐波分量来检测熄灭的电弧瞬间。 ORT是由同步发电机的负载角得出的。所提出的集成技术取决于自适应阈值水平以及仅从一端捕获的信息。在电压和速度指标方面,与传统的重合闸方案相比,对综合重合闸方法的性能进行了评估。通过使用MATLAB / SIMULINK来仿真单机无限总线系统模型(SIME),可以确认集成方法。输出结果表明,所提出的重合闸方法可以提高暂态稳定性。