首页> 外文会议>International conference on control, automation and systems >Temporary primary frequency control support by deloaded wind power plant using input-output linearization
【24h】

Temporary primary frequency control support by deloaded wind power plant using input-output linearization

机译:使用输入输出线性化的风力发电站的临时一次频率控制支持

获取原文

摘要

In this paper, a nonlinear control method is proposed to improve the primary frequency control for doubly fed induction generator (DFIG) wind turbine system. Individual wind turbines in wind power plant are controlled in deloaded operation to provide the frequency support during depressed frequency conditions. By considering of nonlinearity of the system, input-output linearization method is applied to improve the performance of primary frequency response. It can be guaranteed that the system is exponentially stable with the proposed method. The proposed method is validated by using a simple microgrid, consisting of one wind power plant, one diesel generator, and a load, through MATLAB/Simulink. The simulation results show that the proposed method has an improvement of primary frequency control when the load increases.
机译:本文提出了一种非线性控制方法来改善双馈感应发电机(DFIG)风力发电机系统的主频率控制。风力发电厂中的单个风力涡轮机在卸载操作中受到控制,以在频率降低的情况下提供频率支持。考虑到系统的非线性,采用输入输出线性化的方法来提高一次频率响应的性能。所提出的方法可以保证系统是指数稳定的。通过使用一个简单的微电网(包括一个风力发电厂,一个柴油发电机和一个负载),通过MATLAB / Simulink对所提出的方法进行了验证。仿真结果表明,该方法在负载增加时对一次频率控制具有改进作用。