In this paper the operating times of high voltage SF6 live tank circuit breakers are tested using standard timing tests. The time measurements obtained have proven to be adequate to the normal distribution. The hypothesis testing methodology is applied in order to determine the mean difference value between the tested phase operating times. The results obtained showed that the time difference between the operating times of the tested circuit breakers is located between -0.661 and 0.536 ms, which indicates that the operating mechanism of the breakers is still reliable and in good condition.
机译:在本文中,使用标准定时测试来测试高压SF6活性油箱断路器的工作时间。已证明获得的时间测量值足以满足正态分布。应用假设测试方法来确定测试阶段运行时间之间的平均差值。所获得的结果表明,被测试的断路器的工作时间之间的时间差在-0.661到0.536 ms之间,这表明断路器的工作机制仍然可靠并且处于良好状态。