首页> 外文会议>International Conference on AC and DC Power Transmission >The study on CT saturation caused by the circulating current in the delta-winding of converter transformer and its impact on the protection in HVDC system
【24h】

The study on CT saturation caused by the circulating current in the delta-winding of converter transformer and its impact on the protection in HVDC system

机译:换流变压器三角形绕组中循环电流引起的CT饱和及其对高压直流输电系统保护的影响

获取原文

摘要

In the typical HVDC power system, the current transformers (CTs) between the Y-delta converter transformer and the converter bridge is located in the delta-winding of the transformer. Under such condition, the measuring current of these CTs includes the zero-sequence circulating current of the delta-winding. In the case of the adjacent transformer energization or the fault of AC system, the zero-sequence circulating current in the delta-winding maybe very large containing a great amount of dc component. Thus the CTs will be saturated, resulting in the misoperation of the relevant protection in HVDC system, such as the bridge current differential protection. This sort of misoperation seriously threatens the safe and sound operation of the HVDC power system. In this paper, the misoperation cause is analysed in detail via the PSCAD/EMTDC-based simulation. Based on this, a method is proposed to prevent this sort of misoperation by utilizing the zero-sequence circulating current as the restraint quantity.
机译:在典型的HVDC电力系统中,Y三角形转换器变压器和转换器桥之间的电流互感器(CT)位于变压器的三角形绕组中。在这种情况下,这些CT的测量电流包括三角形绕组的零序循环电流。在相邻的变压器通电或交流系统出现故障的情况下,三角形绕组中的零序循环电流可能会非常大,其中包含大量的直流分量。因此,电流互感器将饱和,从而导致HVDC系统中的相关保护(例如电桥电流差动保护)误操作。这种误操作严重威胁了HVDC电力系统的安全和良好运行。在本文中,通过基于PSCAD / EMTDC的仿真对误操作原因进行了详细分析。基于此,提出了一种以零序循环电流为约束量来防止这种误操作的方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号