首页> 外文会议>International Conference on Intelligent Computer Communication and Processing >Thermal aware workload consolidation in cloud data centers
【24h】

Thermal aware workload consolidation in cloud data centers

机译:云数据中心中的热感知工作负载整合

获取原文

摘要

This paper addresses the problem of Data Centers (DC) energy efficiency by proposing a complex consolidation technique which aims at optimizing the DC operation such that both the IT equipment power consumption and cooling system power consumption is minimized. The paper presents a thermo-electrical DC model that defines the relation between the server utilization due to VM deployment, the server room ambient temperature and the cooling system load needed to dissipate the corresponding heat. Furthermore, a set of approximation algorithms and heuristics are presented to solve the resulting NP-hard thermal-aware consolidation problem. Finally, simulation results on some predefined scenarios show that the proposed techniques improve the DC energy consumption with 5% up to 20% compared to the well-known First-Fit algorithm by deploying VMs on servers with low thermal influence. This allows the cooling system to increase its air supply temperature with up to 10 degrees Celsius, leading to lower power consumption.
机译:本文通过提出一种复杂的整合技术来解决数据中心(DC)的能源效率问题,该技术旨在优化DC操作,从而最大程度地降低IT设备功耗和冷却系统功耗。本文提出了一个热电直流模型,该模型定义了由于虚拟机部署而导致的服务器利用率,服务器机房环境温度以及散发相应热量所需的冷却系统负载之间的关系。此外,提出了一组近似算法和启发式方法来解决由此产生的NP-hard热感知合并问题。最后,在一些预定义的方案上的仿真结果表明,与众所周知的First-Fit算法相比,通过在热量影响较小的服务器上部署VM,所提出的技术可将DC能耗降低5%至20%。这允许冷却系统将其空气供应温度提高多达10摄氏度,从而降低了功耗。