首页> 外文会议>International Conference on Advances in Electrical, Electronics, Information, Communication and Bio-Informatics >Optimum location of superconducting fault current limiter to mitigate DG impact
【24h】

Optimum location of superconducting fault current limiter to mitigate DG impact

机译:超导故障限流器的最佳位置,以减轻DG的影响

获取原文

摘要

The penetration of Distributed Generation (DG) changes the fault current level and direction. This leads to violate the relay coordination in the power system network. Superconducting fault current limiters (SFCLs) are commonly used to minimize the fault current level to restore original relay coordination. This paper presents the optimum location of the SFCL to limit the fault current level with minimum size and cost of SFCL. The restoration of protection coordination is carried out without changing the original relay settings or disconnecting DG from power system network during fault conditions. In this work, a resistive type SFCL is presented to minimize the fault current level. A typical power system model including generation, transmission and distribution network with DG is presented to determine the optimum location and the performance of the SFCL. Three phase faults are simulated at different locations in the power system and the effect of DG of fault current is evaluated. Accordingly, the optimum arrangement of the SFCL location in power system with DG has been proposed.
机译:分布式发电(DG)的渗透会改变故障电流的水平和方向。这导致违反电力系统网络中的继电器协调。超导故障电流限制器(SFCL)通常用于使故障电流水平最小化,以恢复原始继电器的协调性。本文提出了SFCL的最佳位置,以最小的SFCL尺寸和成本来限制故障电流水平。在故障情况下,无需更改原始继电器设置或断开DG与电力系统网络的连接即可恢复保护协调。在这项工作中,提出了一种电阻型SFCL,以最大程度地降低故障电流水平。提出了一个典型的电力系统模型,包括带有DG的发电,输电和配电网络,以确定SFCL的最佳位置和性能。在电力系统的不同位置模拟了三相故障,并评估了故障电流DG的影响。因此,已经提出了在具有DG的电力系统中SFCL位置的最佳布置。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号