Protection current transformers (CTs) should be tested both before installation and during a maintenance program to assure their correct operation. Realizing the existence of a high number of installed CTs in an interconnected power grid would make this procedure costly and time consuming. This paper describes how to develop an economic, accurate, and time-efficient microprocessor-based CT test set. A full-bridge inverter is utilized to generate a novel time-efficient voltage signal to measure the required CT parameters. Using a fast discrete wavelet denoising algorithm empowers the test set to be used for actual on-site application where the measured signals are highly contaminated with the plant noise. The validity of the proposed method is verified against a wide range of real experimental results. The results emphasize that the method is effective, reliable, and accurate.
机译:保护电流互感器(CT)应当在安装之前和维护程序中进行测试,以确保其正确运行。实现互连电网中大量已安装的CT的存在将使此过程既昂贵又耗时。本文介绍了如何开发一种经济,准确,省时的基于微处理器的CT测试仪。全桥逆变器用于生成新颖的省时电压信号,以测量所需的CT参数。使用快速离散小波去噪算法可以使测试集用于实际现场应用,在这种情况下,被测信号被植物噪声高度污染。针对大量实际实验结果验证了该方法的有效性。结果表明,该方法有效,可靠,准确。