首页> 外文会议>Iranian Conference on Electrical Engineering >Accurate protection current transformer parameters determination method under high noise immunity
【24h】

Accurate protection current transformer parameters determination method under high noise immunity

机译:高噪声免疫力下的精确保护电流互感器参数测定方法

获取原文

摘要

Protection current transformers (CTs) should be tested both before installation and during a maintenance program to assure their correct operation. Realizing the existence of a high number of installed CTs in an interconnected power grid would make this procedure costly and time consuming. This paper describes how to develop an economic, accurate, and time-efficient microprocessor-based CT test set. A full-bridge inverter is utilized to generate a novel time-efficient voltage signal to measure the required CT parameters. Using a fast discrete wavelet denoising algorithm empowers the test set to be used for actual on-site application where the measured signals are highly contaminated with the plant noise. The validity of the proposed method is verified against a wide range of real experimental results. The results emphasize that the method is effective, reliable, and accurate.
机译:保护电流互感器(CTS)应在安装之前和维护程序期间进行测试,以确保其正确的操作。实现在互联电网中的大量安装CTS的存在将使此过程昂贵且耗时。本文介绍了如何开发经济,准确和延时的基于微处理器的CT测试集。使用全桥式逆变器用于产生新的延时电压信号以测量所需的CT参数。使用快速离散小波去噪算法使得测试集用于实际的现场应用,其中测量的信号受到植物噪声的高度污染。拟议方法的有效性针对各种实验结果验证。结果强调该方法有效,可靠,准确。