Refrigeration systems play paramount roles in life quality of human beings and social development in terms of food security, environmental impact, and energy efficiency. The traditional CFC, HCFC, and HFC refrigerants have been in the process of phase-out and being replaced by the sustainable working fluids. In this paper, the experimental thermodynamic performance evaluation of the hydrocarbons R600a, R290 and their mixtures used in a vapour compression refrigeration system that utilizes R134a as a working fluid was carried out. Firstly, a theoretical analysis was developed to evaluate the feasibility of the retrofit by employing the vapour compression refrigeration cycle. The evaporation temperatures were ranging from −25 °C to 3 °C, and the condensation temperatures ranging from 25 °C to 65 °C with superheating and subcooling degrees constant at 5 °C. The thermodynamic and thermophysical properties were obtained using REFPROP software. Lastly, based on the results obtained from the theoretical analysis, the experimental comparison of the refrigeration cycle performance was conducted using a refrigeration system designed for R134a. The results show that both pure R600a and R290 cannot be recommended as drop-in substitutes for R134a due to their significant differences in thermophysical properties. A mixture of R600a/R290 50%/50% composition was found to be the most appropriate alternative refrigerant for the R134a system retrofit with a comparative thermal performance.
机译:就食品安全,环境影响和能源效率而言,制冷系统在人类的生活质量和社会发展中发挥着至关重要的作用。传统的CFC,HCFC和HFC制冷剂已处于逐步淘汰阶段,并被可持续的工作流体所取代。本文对使用R134a作为工作流体的蒸汽压缩制冷系统中的碳氢化合物R600a,R290及其混合物进行了热力学性能实验评估。首先,进行了理论分析,以评估采用蒸汽压缩制冷循环进行改造的可行性。蒸发温度范围为-25°C至3°C,冷凝温度范围为25°C至65°C,其中过热度和过冷度恒定为5°C。使用REFPROP软件获得热力学和热物理性质。最后,基于理论分析的结果,使用为R134a设计的制冷系统进行了制冷循环性能的实验比较。结果表明,纯R600a和R290均不建议作为R134a的直接替代品,因为它们在热物理性质上存在显着差异。发现R600a / R290 50%/ 50%成分的混合物是具有相对热性能的R134a系统翻新的最合适的替代制冷剂。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号