首页> 外文会议>International Conference on Modelling, Identification and Control >The Impacts of Distributed Doubly-Fed Induction Generators onSmart Distribution Grid Protection
【24h】

The Impacts of Distributed Doubly-Fed Induction Generators onSmart Distribution Grid Protection

机译:分布式双馈诱导发电机的影响贴功式分布网格保护

获取原文

摘要

Doubly-fed induction generators (DFIG) used an AC-DC-AC power converter to excite the machine and connected crowbar protection in its rotor side, which makes fault characteristic differ from the synchronic generator's. That may bring problems to traditional current protection in distribution grid. Also, DFIG as a distributed generator (DG) had capability of Fault Ride-Through (FRT), but the tripping principles of the protection installed at point of -common coupling (PCC) may disconnect DG when a fault occurred in the Grid. Based on the short circuit current analysis concerned its magnitude and decay time, a compounded current-voltage protection at the PCC is proposed. That scheme could overcome "negative" impact on protection caused by fault current characteristic of DFIG and ensure the DFIG operate under FRT when a fault happens in distribution network..
机译:双馈诱导发电机(DFIG)使用AC-DC-AC电源转换器激发机器并在其转子侧连接撬棍保护,这使得故障特性与同步发电机不同的情况不同。这可能会对分销网格中的传统电流保护带来问题。此外,作为分布式发电机(DG)的DFIG具有故障驾驶(FRT)的能力,但是当在电网中发生故障时,安装在--Common耦合点(PCC)的跳闸原理可以断开DG。基于短路电流分析涉及其幅度和衰减时间,提出了PCC的复合电流电压保护。该方案可以克服“消极”影响对DFIG故障电流特性引起的保护,并确保在分销网络中发生故障时,在FRT下,DFIG在FRT下运行。