首页> 外文会议>Annual Conference for Protective Relay Engineers >GSU transformer - Current transformer connections and differential relay applications
【24h】

GSU transformer - Current transformer connections and differential relay applications

机译:GSU变压器-电流互感器连接和差动继电器应用

获取原文

摘要

The application and connection of current transformers for electromechanical differential circuits creates vulnerability for mis-operation under rare but identified scenarios. As a lesson learned from a real-world incident, discovery of the vulnerability occurred during the investigation of a generating unit trip from a nearby switchyard fault immediately outside a generator step-up transformer (GSU) differential zone of protection. Problem resolution is correctable or minimized with the available features of microprocessor differential relays, with sufficient winding inputs, and the proper application of current transformer connections. However, shortcuts in the design and installation of new circuits and microprocessor relays can introduce similar vulnerabilities.
机译:机电差动电路中电流互感器的应用和连接在极少数但已确定的情况下容易造成误操作。从现实事件中汲取的教训是,在调查发电机组因发电机升压变压器(GSU)差动保护区域外的附近开关厂故障而跳闸期间,发现了该漏洞。利用微处理器差分继电器的可用功能,足够的绕组输入以及电流互感器连接的正确应用,可以解决或最小化问题的解决方案。但是,设计和安装新电路以及微处理器继电器的捷径可能会引入类似的漏洞。