High-speed current-balance relaying has been subject to occasional false tripping that has not been explained satisfactorily. Field and factory tests now show that this is probably due to differences in residual fluxes in the current-transformer cores. The limiting value of these fluxes can be calculated approximately, and they can be measured with portable instruments connected to the secondary winding. They may cause a deficiency in secondary current, especially during the first half-cycle of fault current, which will cause current-balance or differential-overcurrent relays to operate falsely. This false operation can be avoided by the addition of a short inherent or external time delay with relays having a high dropout, or by the use of special current transformers.
机译:高速电流平衡继电器偶尔会出现误跳闸现象,目前还没有令人满意的解释。现在,现场和工厂测试表明,这可能是由于电流互感器铁芯中的剩余磁通量不同所致。这些通量的极限值可以近似计算,并且可以使用连接到次级绕组的便携式仪器进行测量。它们可能会导致次级电流不足,尤其是在故障电流的前半个周期中,这会导致电流平衡或差分过电流继电器误动作。可以通过使用具有高压降的继电器增加较短的固有或外部时间延迟,或通过使用特殊的电流互感器来避免这种错误操作。