摘要

Voltage feed-forward control (VFFC) is widely used due to its good low-frequency-harmonics suppression and easy implementation, however, it will worsen system stability under the weak grid condition. In this paper, the stability of single-phase grid-connected inverter with VFFC is studied based on impedance analysis method. With this method, the instability mechanism and the unstable area caused by VFFC are easily obtained. Based on this, system can be stabilized simply by adding phase-lead compensation, avoiding the real-time detection of grid impedance. Simulation and experimental results verify the analysis and the proposed control method.
机译:由于其良好的低频 - 谐波抑制和易于实现,电压前馈控制(VFFC)被广泛使用,但是,在弱网格条件下,它将恶化系统稳定性。本文研究了基于阻抗分析方法研究了具有VFFC的单相网连接逆变器的稳定性。利用这种方法,容易获得由VFFC引起的不稳定机制和不稳定区域。基于此,通过添加阶段铅补偿,可以简单地稳定系统,避免网格阻抗的实时检测。仿真和实验结果验证了分析和所提出的控制方法。