首页> 外文会议>International Conference on Electrical Machines and Systems >Modified DPC for DFIG based wind power generation under unbalanced grid-voltage
【24h】

Modified DPC for DFIG based wind power generation under unbalanced grid-voltage

机译:不平衡电网下基于DFIG的风力发电的修改DPC

获取原文

摘要

This paper presents a modified direct power control (DPC) strategy for a doubly fed induction generator (DFIG) based wind power generation system under unbalanced grid-voltage conditions. The strategy is based on the investigation of the mathematic model and the composition of the instantaneous active and reactive power outputted by DFIG. It is found that, by applying a notch filter of two times of the grid frequency, the proposed DPC strategy is capable of the unbalanced fault ride through operation. By compensating the errors caused by DFIG parameter mismatch, the control robustness of the proposed DPC scheme has been further enhanced. Simulation results verified that the proposed strategy is simple in control structure and have excellent dynamic performance for the reason of avoiding the computation of the negative sequence component current, and therefore, the corresponding current control loops are unnecessary.
机译:本文介绍了在不平衡网格 - 电压条件下基于双馈电流发电机(DFIG)的风力发电系统的改进的直接电源控制(DPC)策略。该策略基于对数学模型的调查和DFIG输出的瞬时主动和无功功率的组成。结果发现,通过应用两次电网频率的凹口滤波器,所提出的DPC策略能够通过操作来乘坐不平衡的故障。通过补偿由DFIG参数不匹配引起的误差,进一步提高了所提出的DPC方案的控制稳健性。仿真结果证明了所提出的策略在控制结构中简单,具有出色的动态性能,从而避免了负序分量电流的计算,因此,不需要相应的电流控制环。