Unsynchronized fault location independent on line parameters for transmission systems

机译:独立于传输系统线路参数的非同步故障定位

获取原文

摘要

In this paper, an improved double-end fault locator is presented for transmission systems using unsynchronized measurements and disregarding the line parameters. The proposed algorithm is formalized using lumped parameter line model in order to facilitate computing the unsynchronized shifting angle between both line ends. The Least Square Error (LSE) is first used to solve the equivalent positive sequence network of the line using double end measurements to compute the synchronizing angle. Artificial Neural Network is then utilized to minimize the errors in angle extraction and accordingly the fault distance is estimated correctly. The ATP-EMTP program is used to perform the fault cases and therefore evaluating the locator performance. The test results provide evidences for the efficacy of the proposed fault locator using unsynchronized double end measurements without utilizing the line parameters for any fault type.
机译:在本文中,提出了一种改进的输电系统双端故障定位仪,它使用了不同步的测量方法而忽略了线路参数。使用集总参数线模型对提出的算法进行形式化,以便于计算线两端之间的不同步移位角。最小二乘误差(LSE)首先用于使用双端测量来计算同步角来求解线的等效正序网络。然后利用人工神经网络将角度提取中的误差降到最低,从而正确估计故障距离。 ATP-EMTP程序用于执行故障情况,并因此评估定位器性能。测试结果为使用不同步的双端测量而没有利用任何故障类型的线路参数的建议故障定位器的有效性提供了证据。