首页> 外文会议>IEEE/IAS International Conference on Industry Applications >Robust #x210C;#x221E; control for grid connected PWM inverters with LCL filters
【24h】

Robust #x210C;#x221E; control for grid connected PWM inverters with LCL filters

机译:具有LCL滤波器的电网连接PWM逆变器的强大控制

获取原文

摘要

This paper provides a robust control design based on linear matrix inequalities applied to PWM inverters with LCL filters connected to the grid under uncertain parameters. The proposed controller ensures: i) closed-loop robust stability against parameter uncertainty; ii) robust pole location with a prescribed ℌ guaranteed cost; iii) tracking of sinusoidal reference and rejection of disturbances. Simulation and experimental results show good transient and frequency responses for the closed-loop system, as well as limits of robust stability.
机译:本文提供了一种基于线性矩阵不等式的鲁棒控制设计,其应用于PWM逆变器,LCL滤波器在不确定参数下连接到网格。所提出的控制器可确保:i)闭环稳健稳定性,免受参数不确定性的稳定性; ii)具有规定的杆位置的强大杆位置ℌ保证费用; iii)跟踪正弦参考和扰动的排斥。仿真和实验结果显示闭环系统的良好瞬态和频率响应,以及鲁棒稳定性的限制。