首页> 外文会议>International symposium on heating, ventilation and air conditioning >Exergy Analysis of a Ground Source Heat Pump System Under Cooling and Heating Conditions
【24h】

Exergy Analysis of a Ground Source Heat Pump System Under Cooling and Heating Conditions

机译:冷热条件下地源热泵系统的火用分析

获取原文
获取外文期刊封面目录资料

摘要

Energy and exergy analyses models were established to evaluate the performance of a ground source heat pump (GSHP) based on the energy conservation and the exergy destruction principles. The GSHP supplies cooling water and hot water to the air handling unit of a building air-conditioning system in cooling and heating season, respectively. It rejects and absorbs heat from the soil through borehole heat exchangers accordingly. The models were programmed and the properties of the working mediums were calculated by calling the software REFPROP. Results indicate that GSHP system operates at higher exergy efficiency in heating mode. The exergy efficiencies of the whole system are 23.07 and 34.31 % in cooling and heating modes, respectively. And the performances of every component are evaluated.
机译:建立了能源和火用分析模型,以基于节能和火用破坏原理评估地源热泵(GSHP)的性能。 GSHP在制冷和制热季节分别向建筑空调系统的空气处理单元供应冷却水和热水。它通过钻孔热交换器从土壤中排走并吸收热量。通过调用软件REFPROP对模型进行编程并计算工作介质的属性。结果表明,GSHP系统在加热模式下以更高的火用效率运行。在冷却和加热模式下,整个系统的火用效率分别为23.07%和34.31%。并评估每个组件的性能。