The safe operation of power transformers in electrical network is crucial to the reliable of electrical power supply. Under electrical and thermal stresses, the insulation system will be degraded and increases the risk of transformer failure. The used of various diagnostic tools are become important to detect ageing and faults to avoid catastrophic failures. This paper presents the analysis results of dielectric response in time domain known as Polarization Depolarization Current (PDC) measurement on mineral insulating transformer oil under partial discharge, overheating and arcing conditions. The analysis result on the PDC pattern had show that arcing fault has higher polarization and depolarization current magnitude at the initial response compared to partial discharge and overheating fault. It concluded that faults in power transformer changes the oil properties and thus affect the dielectric response of the oil.
机译:电网中电力变压器的安全运行对于供电的可靠性至关重要。在电和热应力下,绝缘系统将退化并增加变压器故障的风险。各种诊断工具的使用对于检测老化和故障以避免灾难性故障变得很重要。本文介绍了矿物绝缘变压器油在局部放电,过热和电弧放电条件下的时域介电响应分析结果,即极化去极化电流(PDC)测量。对PDC模式的分析结果表明,与局部放电和过热故障相比,电弧故障在初始响应时具有更高的极化和去极化电流幅度。结论是电力变压器的故障改变了油的特性,从而影响了油的介电响应。