首页> 外文会议>Annual Conference for Protective Relay Engineers >Addressing protection challenges associated with Type 3 and Type 4 wind turbine generators
【24h】

Addressing protection challenges associated with Type 3 and Type 4 wind turbine generators

机译:解决与3型和4型风力涡轮发电机相关的保护挑战

获取原文

摘要

Variable-speed doubly fed asynchronous (Type 3) and full converter-based (Type 4) wind turbine generators (WTGs) have complex fault current characteristics governed by proprietary controls. The control technique of some manufacturers is to produce balanced three-phase fault current during unbalanced faults. At present, short-circuit analysis tools commonly used by protection engineers are inadequate in representing the fault current behavior of these WTGs. This paper presents the fault current characteristics of a Type 4 WTG using a detailed MATLAB and Simulink model that incorporates pseudo control logic for this converter type. This paper also presents a case study of a misoperation of directional overcurrent relays connected to the collector circuit in an actual wind power plant during a fault. The paper provides recommendations on protecting wind power plants with these converter-based WTGs.
机译:变速倍增异步(类型3)和基于完整的转换器(类型)风力涡轮发电机(WTG)具有由专有控制管理的复杂故障电流特性。一些制造商的控制技术是在不平衡故障期间产生平衡的三相故障电流。目前,保护工程师常用的短路分析工具在代表这些WTG的故障当前行为时不足。本文使用详细的MATLAB和SIMULINK模型介绍了4型WTG的故障电流特性,该模型包含该转换器类型的伪控制逻辑。本文还提出了一种在故障期间连接到实际风力发电厂中的集电泵的定向过电流继电器的误操作的案例研究。本文提出了有关保护风电厂与基于转换器的WTG的建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号