Feeder Interruptions Caused by Recurring Faults on Distribution Feeders: Faults You Don't Know About

机译:通过在配送送料器上的故障引起的饲养器中断:您不了解的故障

获取原文

摘要

Weather, equipment failure, and contact by foreign objects cause faults, trips, interruptions, and outages. Most faults are either permanent, requiring repairs before service can be restored, or truly temporary, causing no lasting impairment to the system. Monitoring programs at Texas A&M University have instrumented dozens of feeders at North American utility companies for multiple years. Sensitive monitoring and recording systems have documented multiple instances in which failing apparatus, vegetation intrusion, and other factors have caused multiple faults and momentary interruptions, over significant periods of time, without causing sustained outages. A recurrent fault can easily escape notice when a pole-mount recloser is the interrupting device, because there often is no telemetry (e.g., SCADA) to report that anything happened. Even recurrent faults that trip a substation breaker can escape notice when time intervals between operations are sufficiently long for operator memories to fade. Fault current and arcing from recurrent faults can further damage already weak apparatus, eventually causing a permanent outage, at which time there may be more consequential damage to apparatus, including burned-down lines. This paper documents multiple examples of recurrent faults and interruptions, including their causes and consequences. It also documents other events that cause poor power quality and/or reliability after a significant period in which a degraded condition produces electrical "warning signs." These "warning signs" have always been present on feeders but they could not be used to prevent or mitigate problems because the symptoms previously were unknown or inadequately understood.
机译:天气,设备故障和外国对象的联系导致故障,旅行,中断和中断。大多数故障是永久性的,需要在恢复服务之前维修,或者真正暂时维修,从而不会对系统持久损害。德克萨斯州A&M大学的监测计划在北美公用事业公司的数十家饲养器中有多年来。敏感的监控和记录系统记录了多种情况,其中失败的装置,植被侵入和其他因素导致多个故障和瞬间中断,在没有引起持续的中断。当杆安装重闭器是中断设备时,复发故障可以轻松地逃脱注意,因为通常没有遥测(例如,SCADA)报告发生的事情。甚至绊倒变电站断路器的反复出现故障可以在操作员存储器越来越长的时间间隔足够长时间时逃脱注意。来自反复出现故障的故障电流和电弧机会可以进一步损坏已经弱的设备,最终导致永久性停机,此时对设备可能会受到更大的影响,包括烧毁线。本文记录了多次反复出现故障和中断的例子,包括它们的原因和后果。它还记录了在重大期间在劣化条件产生电气“警告标志”的重要时期后引起功率质量和/或可靠性的其他事件。这些“警告标志”一直存在于馈线上,但它们不能用于预防或减轻问题,因为之前的症状未知或不充分理解。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号