首页> 外文会议>Annual Conference of the IEEE Industrial Electronics Society >Negative sequence based relay operate area approach to detect transformer inter-turn fault
【24h】

Negative sequence based relay operate area approach to detect transformer inter-turn fault

机译:基于负序列的继电器操作区域方法来检测变压器的变压器间故障

获取原文

摘要

This article presents a new approach for transformer inter-turn fault detection. Conventional differential scheme is provided with bias to prevent mal-operation in case of over-excitation, CT saturation, magnetising inrush, etc. However, this prevents conventional scheme from detecting inter-turn fault at incipient stage where less turns are involved in the fault. Proposed scheme overcomes this drawback by introducing Relay Operate Area (ROA) approach. The proposed two stage approach initially detects presence of fault and later confirms the presence for observation based on predefined loading conditions. Experimental results on laboratory transformer are presented which confirms the proposed approach.
机译:本文介绍了变压器匝间故障检测的新方法。 传统的差分方案被提供有偏差,以防止在过励磁,CT饱和,磁化浪涌等的情况下防止发生的MAL操作。然而,这防止了传统方案在故障中涉及较少的阶段的初期阶段检测变频故障 。 建议方案通过引入继电器操作区域(ROA)方法来克服了该缺点。 所提出的两级方法最初检测出故障的存在,后来证实了基于预定负载条件的观察的存在。 提出了实验室变压器的实验结果,证实了所提出的方法。