首页> 外文会议>North American Power Symposium >System-Wide Case Study Assessment of Transformer Heating Due to Geomagnetic Disturbances
【24h】

System-Wide Case Study Assessment of Transformer Heating Due to Geomagnetic Disturbances

机译:岩石紊乱导致变压器加热的全系统案例研究

获取原文

摘要

The geomagnetically induced currents (GICs) are a potentially catastrophic threat to large-scale power system operations especially the bulk transformers, possibly leading to severe outages. This paper provides a system-wide transformer temperature analysis due to GIC-induced half-cycle saturation. The derived thermal assessment model identifies the potential overheated transformers in a geomagnetic disturbance (GMD) event and characterizes the relationship between the GIC and the transformer's temperature response. The suggested approach is applied to the 20-bus GIC benchmark test case facing a GMD event, where the time-varying temperature responses are evaluated and numerically analyzed in both normal and hotspot contingency scenarios.
机译:地磁诱导的电流(GICS)对大型电力系统操作尤其是散装变压器可能导致严重停电的可能性灾难性的威胁。本文由于GIC诱导的半循环饱和度,提供了一种系统宽的变压器温度分析。导出的热评估模型识别在地磁干扰(GMD)事件中的潜在过热的变压器,并表征了GIC与变压器的温度响应之​​间的关系。建议的方法应用于面对GMD事件的20-BUS GIC基准测试用例,其中在正常和热点应急场景中评估和数值分析了时变温响应。