首页> 外文会议>IEEE/IAS Industrial Commercial Power Systems Technical Conference >Ground-fault loop impedance calculations in single-phase systems
【24h】

Ground-fault loop impedance calculations in single-phase systems

机译:单相系统中的接地故障回路阻抗计算

获取原文

摘要

Protection against electric shock in low-voltage installations by automatic disconnection of the supply must be provided in compliance with applicable national or international standards. Such regulations (e.g. National Electrical Code in the U.S., IEC 60364, BS 7671 in the U.K., etc.) take into account the earthing system of the installation, such as TT, TN-C-S, or IT systems. To realize the protection against indirect contact, the disconnection of the supply must occur within a permissible safe time. To this purpose, the determination of the actual ground fault-loop impedance (which may, or may not, comprise the earth) is essential. This impedance, in fact, must not exceed a maximum value, so that a sufficient ground-fault current can circulate and operate protective devices within the safe time. In some instances, explained in this paper, safety might be achieved, or increased, by converting one earthing system into another (e.g. from TT to TN, from TN to TT, from TN-C to TN-S, etc.), by means of single-phase transformers. This conversion can be promoted by either utilities or users. Other cases of conversion of grounding type, although not driven by safety concerns, are also examined, as they can be used to study the influence of neutral earthing on single-phase short-circuits. This paper seeks to clarify the circuits to be employed for the calculation of ground fault-loop impedances when the earthing type changes across single-phase transformers. The quantitative analysis of this topic is not present in current technical standards.
机译:必须按照适用的国家或国际标准,通过自动断开电源来保护低压设备中的电击。此类规定(例如美国的国家电气法规,IEC 60364,英国的BS 7671等)考虑了设备的接地系统,例如TT,TN-C-S或IT系统。为了实现防止间接接触的保护,必须在允许的安全时间内断开电源。为此,必须确定实际的接地故障环路阻抗(可能包括也可能不包括大地)。实际上,该阻抗不得超过最大值,以使足够的接地故障电流可以在安全时间内循环并操作保护设备。在某些情况下,如本文所述,通过将一个接地系统转换为另一个接地系统(例如,从TT到TN,从TN到TT,从TN-C到TN-S等),可以实现或提高安全性。单相变压器的手段。实用程序或用户均可促进此转换。尽管不是出于安全考虑,但也检查了接地类型转换的其他情况,因为它们可用于研究中性点接地对单相短路的影响。本文试图阐明当单相变压器的接地类型发生变化时,用于计算接地故障回路阻抗的电路。当前技术标准中不存在对此主题的定量分析。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号