首页> 外文会议>European Conference on Power Electronics and Applications >Construction of a current injection unit for marine applications
【24h】

Construction of a current injection unit for marine applications

机译:建造目前用于船舶的注入装置

获取原文

摘要

This paper presents the design and operation of a portable Current Injection Unit (CIU) to be used in conjunction with the Active Impedance Estimation (AIE) technique for fault location in DC electrical distribution systems. The AIE technique injects a current transient into the system and monitors the resultant voltage transient. By combining these measurements in the frequency domain, the real and reactive components of system impedance can be estimated and the reactance can be used to indicate fault location. The prototype has been tested experimentally for short circuit faults and is shown to be effective. The portable unit can be used to test the AIE algorithm on more complex DC distribution systems.
机译:本文介绍了便携式电流注入单元(CIU)的设计和操作,该单元将与有源阻抗估计(AIE)技术一起用于直流配电系统中的故障定位。 AIE技术将电流瞬变注入系统并监视所得的电压瞬变。通过在频域中组合这些测量,可以估算系统阻抗的有功和无功分量,并且可以使用电抗来指示故障位置。该原型已针对短路故障进行了实验测试,并被证明是有效的。便携式单元可用于在更复杂的DC配电系统上测试AIE算法。