Investigation on partial discharge of power cable termination defects using High Frequency Current Transformer

机译:使用高频电流互感器对电力电缆终端缺陷局部放电的研究

获取原文

摘要

This paper presents partial discharge (PD) investigation of different cable termination defects. The medium voltage power cables as rated of 3.6/7 (7.2) kV are applied. The partial discharges pattern of each case is detected by using a commercial High Frequency Current Transformer (HFCT). The simple cases for internal, surface and corona discharge are firstly observed in order to investigate the performance of the HFCT. Then eight different cases studies of cable termination defects are further investigated, which includes non-terminator, voids between XLPE and stress control, 20 mm. overlaps between semiconductor and stress control, particles on XLPE, non-smooth XLPE, needle tip on insulation screen, impropriate cable bending, and proper termination. The results are then compared with the results from a conventional PD diagnosis tool according to IEC 60270 standard. The results of PD detection show that the commercial product can detect the PD waveform and measure the electric charge when it is highly enough. The test can also identify trends toward breakdown and there severity due to improper cable termination defects.
机译:本文介绍了不同电缆端接缺陷的局部放电(PD)研究。使用额定值为3.6 / 7(7.2)kV的中压电力电缆。通过使用商用高频电流互感器(HFCT)可以检测每种情况的局部放电模式。首先观察内部,表面和电晕放电的简单情况,以研究HFCT的性能。然后,对八种不同的电缆端接缺陷案例进行了进一步研究,其中包括非端接器,XLPE与控制应力之间的空隙(20毫米)。半导体和应力控制之间的重叠,XLPE上的颗粒,不光滑的XLPE,绝缘屏蔽层上的针尖,电缆弯曲不当以及正确端接。然后将结果与根据IEC 60270标准的常规PD诊断工具的结果进行比较。 PD检测的结果表明,市售产品足够高时,可以检测到PD波形并测量电荷。该测试还可以确定故障趋势以及由于不正确的电缆端接缺陷而造成的严重性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号