首页> 外文会议>IEEE International Symposium on Applied Computational Intelligence and Informatics >Automatic Generation Control of an interconnected multi-area reheat thermal power systems with conventional proportional-integral controller considering various performance indices
【24h】

Automatic Generation Control of an interconnected multi-area reheat thermal power systems with conventional proportional-integral controller considering various performance indices

机译:考虑各种性能指标的传统比例积分控制器的互连多区域再热动力系统的自动生成控制

获取原文

摘要

This paper presents the analysis of Automatic Generation Control (AGC)/Load Frequency Control (LFC) of conventional three area interconnected thermal power systems. The current study considered suitable Generation Rate Constraints (GRC), reheat and non-reheat turbine. Optimum gain settings of the conventional controllers are obtained, both in the constraints and non-constraints modes using with three different performance indices. Dynamic performance of the system is analyzed considering one percent of step load disturbance is in either area of the system. Furthermore, time domain specification analysis is used for the system performance evaluation. The analysis established that Integral Time Absolute Error (ITAE) based conventional controllers yield better controlled response and good dynamic performance compared to other indices.
机译:本文介绍了传统三个区域互连热电系统的自动生成控制(AGC)/负载频率控制(LFC)的分析。目前的研究考虑了合适的产生率约束(GRC),再加热和非再热涡轮机。使用三种不同的性能指标,在约束和非约束模式下获得传统控制器的最佳增益设置。分析系统的动态性能,考虑到阶梯负荷干扰的一个百分比是系统的任一区域。此外,时间域规范分析用于系统性能评估。该分析确定基于基于时间的传统控制器的积分时间绝对误差(ITAE)产生更好的控制响应和与其他指标相比的良好动态性能。