On-site experience suggests the possibility of condensation of the moisture in Current transformers (CTs) which is impossible theoretically if temperature distribution in the CT is uniform.In order to study the temperature distribution in a typical CT,finite element analysis software (COMSOL Multiphysics) is used to obtain the temperature distribution of the outer surface and inside of SF6 in CT in different ambient temperatures (20 °C to-10 °C).Besides,experiments are conducted to obtain the temperature of different positions on the CT surface that correspond to conductor,shell,spacer and porcelain bushing that are inside the CT with different ambient temperature.Both simulation and experiments show that temperature distribution in the CT is non-uniform,and the closer the part is to the conductor,the higher the temperature.Furthermore,maximum temperature difference remains about 35 °C in both simulation and experiments with different ambient temperatures from 20 °C to-10 °C.
机译:现场经验表明,电流互感器(CT)中可能会凝结水分,如果CT中的温度分布均匀,则理论上是不可能的。为了在典型的CT中研究温度分布,有限元分析软件(COMSOL Multiphysics) )用于获得不同环境温度(20°C至-10°C)下CT中SF6的外表面和内部的温度分布。此外,还进行了实验以获得CT表面上不同位置的温度,仿真和实验均表明,CT中的温度分布不均匀,且部件越靠近导体,温度越高,对应于不同环境温度下CT内的导体,壳体,垫片和瓷套。此外,在从20°C到-10°C的不同环境温度下进行的仿真和实验中,最大温差仍保持在35°C左右。